8800 PowerScope®: Simultaneously monitors voltage, current and environment for all three-phase power disturbances This 8-channel instrument measures three-phase voltage and current simultaneously, making it easy to determine the source of a power quality disturbance. It has 8 additional channels for environmental measurements like temperature, temperature rate-of-change, RFI, and humidity. Or you can use the additional channels to monitor AC or DC voltages.
| Parameter | Specifications |
|---|---|
| Voltage measurements | 4 channels simultaneous User-selected range: 12.5,25, 50,125,333,500, or 1000V Full Scale Sampling rate: 5.12 kHz Accuracy: ±1.0% reading ±0.2% full scale at DC/50/60/400 Hz |
| Current measurements | 4 channels simultaneous Range determined by probe Accuracy: ±1.0% reading ±0.5% full scale at 50/60 Hz Accuracy: ±2.0% reading ±0.5% full scale at 400 Hz |
| Harmonic measurements | Fundamental through 40th at 50Hz Fundamental through 33rd at 60Hz Fundamental through 5th at 400Hz |
| Voltage Impulse measurements | User-selected range to 6,000Vpk Sampling at 4.0 MHz per channel Auto-zoom display |
| Conducted High Frequency Noise | 10kHz - 2.0 Mhz 0.0 - 20.0 V pk-to-pk |
| Battery | NiCad, internally charged 15 minute typical duration User-controlled battery-saving mode |
| Environment | 41°F to 104°F +5°C to +40°C Humidity 0% - 90% non-condensing |
| PC Software package | PES, PowerPlot |
| Latest released version | I/O 2.03 : Math H Acq 2.03 : SPU 2.04 |
Dranetz / BMI 8800